Water metering
Water metering is the practice of measuring water use. Water meters measure the volume of water used by residential and commercial building units that are supplied with water by a public water supply system. They are also used to determine flow through a particular portion of the system.
In most of the world water meters are calibrated in cubic metres or litres, but in the United States and some other countries water meters are calibrated in cubic feet or US gallons on a mechanical or electronic register. Modern meters typically can display rate-of-flow in addition to total volume.
Several types of water meters are in common use, and may be characterized by the flow measurement method, the type of end-user, the required flow rates, and accuracy requirements.
In North America, standards for manufacturing water meters are set by the American Water Works Association. Outside of North America, most countries use ISO standards.
Types of metering devices
There are two common approaches to flow measurement, [|displacement] and [|velocity], each making use of a variety of technologies. Common displacement designs include oscillating piston and nutating disc meters. Velocity-based designs include single- and multi-jet meters and turbine meters.There are also non-mechanical designs, for example, electromagnetic and ultrasonic meters, and meters designed for special uses. Most meters in a typical water distribution system are designed to measure cold potable water only. Specialty hot water meters are designed with materials that can withstand higher temperatures. Meters for reclaimed water have special lavender register covers to signify that the water should not be used for drinking.
Additionally, there are electromechanical meters, like prepaid water meters and automatic meter reading meters. The latter integrates an electronic measurement component and a LCD with a mechanical water meter. Mechanical water meters normally use a reed switch, hall or photoelectric coding register as the signal output. After processing by the microcontroller unit in the electronic module, the data are transmitted to the LCD or output to an information management system.
Water meters are generally owned, read and maintained by a public water provider such as a city, rural water association or private water company. In some cases an owner of a mobile home park, apartment complex or commercial building may be billed by a utility based on the reading of one meter, with the costs shared among the tenants based on some sort of key.
Displacement water meters
are commonly referred to as Positive Displacement, or "PD" meters. Two common types are oscillating piston meters and disk meters. Either method relies on the water to physically displace the moving measuring element in direct proportion to the amount of water that passes through the meter. The piston or disk moves a magnet that drives the register.PD meters are generally very accurate at the low-to-moderate flow rates typical of residential and small commercial users and commonly range in size from 5/8" to 2". Because displacement meters require that all water flows through the meter to "push" the measuring element, they generally are not practical in large commercial applications requiring high flow rates or low-pressure loss. PD meters normally have a built-in strainer to protect the measuring element from rocks or other debris that could stop or break the measuring element. PD meters normally have bronze, brass or plastic bodies with internal measuring chambers made of moulded plastics and stainless steel.
Velocity water meters
A velocity-type meter measures the velocity of flow through a meter of known internal capacity. The speed of the flow can then be converted into a volume of flow to determine the usage. There are several types of meters that measure water flow velocity, including jet meters, turbine meters, propeller meters and mag meters. Most velocity-based meters have an adjustment vane for calibrating the meter to the required accuracy.Multi-jet meters
Multi-jet meters are very accurate in small sizes and are commonly used in ⅝" to 2" sizes for residential and small commercial users. Multi-jet meters use multiple ports surrounding an internal chamber to create multiple jets of water against an impeller, whose rotation speed depends on the velocity of water flow. Multi-jets are very accurate at low flow rates, but there are no large size meters since they do not have the straight-through flow path needed for the high flow rates used in large pipe diameters. Multi-jet meters generally have an internal strainer element that can protect the jet ports from getting clogged. Multi-jet meters normally have bronze alloy bodies or outer casings, with internal measuring parts made from modern thermoplastics and stainless steel.Turbine meters
Turbine meters are less accurate than displacement and jet meters at low flow rates, but the measuring element does not occupy or severely restrict the entire path of flow. The flow direction is generally straight through the meter, allowing for higher flow rates and less pressure loss than displacement-type meters. They are the meter of choice for large commercial users, fire protection and as master meters for the water distribution system. Strainers are generally required to be installed in front of the meter to protect the measuring element from gravel or other debris that could enter the water distribution system. Turbine meters are generally available for 1-½" to 12" or higher pipe sizes. Turbine meter bodies are commonly made of bronze, cast iron or ductile iron. Internal turbine elements can be plastic or non-corrosive metal alloys. They are accurate in normal working conditions but are greatly affected by the flow profile and fluid conditions.- Fire meters are a specialized type of turbine meter meeting the high flow rates requirements for fire protection. They are often approved by Underwriters Laboratories or Factory Mutual for use in fire protection.
- Fire hydrant meters are a specialized type of portable turbine meter attached to a fire hydrant to measure water flowing out of the hydrant. The meters are normally made of aluminium to keep their weight low and usually have a 3" capacity. Utilities often require them for measuring water used on construction sites, for pool filling, or where a permanent meter has not yet been installed.
Compound meters
Electromagnetic meters
s, commonly referred to as "mag meters", are technically a velocity-type water meter, except that they use electromagnetic properties to determine the water flow velocity, rather than the mechanical means used by jet and turbine meters. Mag meters use the physics principle of Faraday's law of induction for measurement and require AC or DC electricity from a power line or battery to operate the electromagnets. Since mag meters have no mechanical measuring element, they normally have the advantage of being able to measure flow in either direction, and use electronics for measuring and totalizing the flow. Mag meters can also be useful for measuring raw water and waste-water since there is no mechanical measuring element to get clogged or damaged by debris flowing through the meter. Strainers are not required with mag meters since there is no measuring element in the stream of flow that could be damaged. Since stray electrical energy flowing through the flow tube can cause inaccurate readings, most mag meters are installed with either grounding rings or grounding electrodes to divert stray electricity away from the electrodes used to measure the flow inside the flow tube.Ultrasonic meters
use one or more ultrasonic transducer to send ultrasonic sound waves through the fluid to determine the velocity of the water. Since the cross-sectional area of the meter body is a fixed and known value, when the velocity of water is detected, the volume of water passing through the meter can be calculated with very high accuracy. Because of water density changes with temperature, most ultrasonic water meters also measure the water temperature as a component of the volume calculation.There are 2 primary ultrasonic measurement technologies used in water metering:
- Doppler effect meters which utilize the Doppler Effect to determine the velocity of water passing through the meter.
- Transit Time meters which measure the amount of time required for the ultrasonic signal to pass between 2 or more fixed points inside the meter.
Ultrasonic water meters are typically very accurate, with residential meters capable of measuring down to 0.01 gallons or 0.001 cubic feet. In addition, they have wide flow measurement ranges, require little maintenance and have long lifespans due to the lack of internal mechanical components to wear out. While relatively new to the American water utility market, ultrasonic meters have been used in commercial applications for many years and are becoming widely accepted due to their advantages over traditional mechanical designs.
Prepaid water meters
Meters can be prepaid or postpaid, depending on the payment method. Most mechanical type water meters are of the postpaid type, as are electromagnetic and ultrasonic meters. With prepaid water meters, the user purchases and prepays for a given amount of water from a vending station. The amount of water credited is entered on media such as an IC or RF type card. The main difference is whether the card needs contact with the processing part of the prepaid water meter. In some areas, a prepaid water meter uses a keypad as the interface for inputting the water credit.Registers
There are several types of registers on water meters. A standard register normally has a dial similar to a clock, with gradations around the perimeter to indicate the measuring unit and the amount of water used, if less than the lowest digit in a display similar to the odometer wheels in a car, their sum is the total volume used. Modern registers are normally driven by a magnetic coupling between a magnet in the measuring chamber attached to the measuring element and another attached to the bottom of the register. Gears in the register convert the motion of the measuring element to the proper usage increment for display on the sweep hand and the odometer-style wheels. Many registers also have a leak detector. This is a small visible disk or hand that is geared closer to the rotation speed of the drive magnet, so that very small flows that would be visually undetectable on the regular sweep hand can be seen.With Automatic Meter Reading, manufacturers have developed pulse or encoder registers to produce electronic output for radio transmitters, reading storage devices, and data logging devices. Pulse meters send a digital or analog electronic pulse to a recording device. Encoder registers have an electronic means permitting an external device to interrogate the register to obtain either the position of the wheels or a stored electronic reading. Frequent transmissions of consumption data can be used to give smart meter functionality.
There are also some specialized types of registers such as meters with an LCD instead of mechanical wheels, and registers to output data or pulses to a variety of recording and controller devices. For industrial applications, the output is often 4-20 mA analog for recording or controlling different flow rates in addition to totalization.
Water meter reading
Different size meters indicate different resolutions of the reading. One rotation of the sweep hand may be equivalent to 10 gallons or to 1,000 gallons. If one rotation of the hand represents 10 gallons, the meter has a 10-gallon sweep. Sometimes the last number of the wheel display are non-rotating or printed on the dial face. The fixed zero number are represented by the position of the rotating sweep hand. For example, if one rotation of the hand is 10 gallons, the sweep hand is on 7, and the wheel display shows 123456 plus a fixed zero, the actual total usage would be 1,234,567 gallons.In the United States most utilities bill only to the nearest 100 or 1,000 gallons, and often only read the leftmost 4 or 5 numbers on the display wheels. Using the above example, they would read and bill 1,234, rounding to 1,234,000 gallons based on a 1,000-gallon billing resolution. The most common rounding for a particular size meter is often indicated by differently coloured number wheels, the ones ignored being black, and the ones used for billing being white.
Prevalence
Water metering is common for residential and commercial drinking water supply in many countries, as well as for industrial self-supply with water. However, it is less common in irrigated agriculture, which is the major water user worldwide. Water metering is also uncommon for piped drinking water supply in rural areas and small towns, although there are examples of successful metering in rural areas in developing countries, such as in El Salvador.Metering of water supplied by utilities to residential, commercial and industrial users is common in most developed countries, except for the United Kingdom where only about 52% of users are metered. In some developing countries metering is very common, such as in Chile where it stands at 96%, while in others it still remains low, such as in Argentina.
The percentage of residential water metering in selected cities in developing countries is as follows:
- 99% in Santiago de Chile
- 96% in Abidjan, Ivory Coast
- 62% in cities in Guatemala
- 30% in Lima, Peru
- 28% in Kathmandu, Nepal
- 2% in Buenos Aires, Argentina
Benefits
The benefits of metering are that:- in conjunction with volumetric pricing it provides an incentive for water conservation,
- it helps to detect water leaks in the distribution network, thus providing a basis for reducing the amount of non-revenue water;
- it is a precondition for quantity-targeting of water subsidies to the poor.
Costs
- Investment costs to purchase, install and replace meters,
- Recurring costs to read meters and issue bills based on consumption instead of bills based on monthly flat fees.